A Queens Public School — Queens, New York — Education
The Situation
In November 2026 the school had no heat. Thermostats showed a Daikin U4-01 communication error, and after a failed reset the facility staff had shut off the disconnect on rooftop condensing unit ACCU-2. Daikin recommended Mountain Mechanical as the VRV specialist for the repair.
What We Found
- The noise-filter board failed during diagnosis with an audible pop and visible smoke
- Compressor No. 2 power leads had been disconnected before our arrival and showed burn marks
- A short in the unit tripped the branch breaker on every reset
- The system’s original design and charge report was not available, so the charge had to be rebuilt from scratch
The Solution
- EPA-certified refrigerant recovery and a full system flush
- Two new Daikin OEM scroll compressors, six circuit boards and two reactors
- Brazing under nitrogen, a standing nitrogen pressure test and evacuation to 300 microns
- Charge weighed in, plus a 33.5 lb R-410A trim charge
- Worked with a Daikin controls specialist to clear the final PJ04 code
Results
ACCU-2 was back in operation on November 17, 2026, after 8 site days from first call to restart, with the work proposed and approved in between.
Project Details
- Location: Queens, NY
- Building: Public school
- System: Daikin VRV heat pump, RXYQ144XATJA (ACCU-2)
- Service: Emergency diagnosis, compressor and board replacement, recommissioning
- Timeline: November 6–17, 2026